● As a sensor for monitoring the cooling water of equipment, acumulative total of 60,000 units have been delivered to leading semiconductor and LCD equipment manufactures in the world.
● Measures and displays the flow rate and temperature.
● Allows use with high temperature water of 90°C.
● Analog output
● Alarm output
● Digital display
Contact us for CAD data and instructions.
*Descriptions are based on Japanese Industrial Standards (JIS).
Specifications
|
Model |
KSL-5L |
KSL-10L |
KSL-30L |
KSL-50L |
Flow range |
0.5-5 L/min |
1.5-10 L/min |
5-30 L/min |
7-50 L/min |
Applicable fluid |
Industrial water or service water |
Maximum working pressure |
1.0 MPa |
Temperature detection range |
0-99°C |
Flow temperature |
0-90°C (No freezing) |
Ambient temperature |
0-40 °C |
Power supply |
DC 12V ± 5% or DC 24V ± 10% |
Current consumption |
30 mA max. (70mA max. in 4 to 20mA specification) |
Cable |
AWM20276 9 core / 0.2 mm? / 500 mm |
red |
Power supply |
|
black |
Ground |
|
white |
Flow rate output (DC0-10V or 4-20mA or Pulse) |
|
orange |
Temperature - detection output |
|
yellow |
Flow rate alarm |
|
green |
Temperature - detection alarm |
|
gray |
Spare core |
|
blue |
Spare core |
|
brown |
Spare core |
Output |
DC0-10V or 4-20mA (Flow rate , temperature) / Pulse (Flow rate) |
Alarm output |
Open collector A or B (Flow rate , temperature) |
O ring |
Fluoro rubber |
Material of body
|
PPS |
Materials of detencors |
PPS (Flow rate detector: PPS, temperature detector: SUS304) |
Adapter size |
Rc3/8" or Rc1/2" |
Adapter material
|
SUS or BsBM + Ni plating |
Accuracy
|
FS ±2.0% |
Flow direction |
Specified derection |
How to order: KSL - 5L - 12V - V- A - A - S - 3/8- Rc
* "P" (pulse output) can be specified only for 5L and 30L and cannot be specified for 10L and 50L.
* When the output of the flow rate is set to "P" (pulse output), the temperature output is "V" or "I."
In temperature output, the pulse output cannot be selected. (The order format of the output is "PV" or "PI.")
Example: KSL-5L-24V-PV-A-B-S-3/8
* The "DPM□" (DPM connection) is a pulse specification for using the external display "DPM□" specified by REGAL JOINT.
* For 50L, only 1/2 can be specified as the adapter connection port diameter.
* To improve the performance, the shape and specifications are subject to change without prior notice.
* The alarm is conductive when the open collector is ON and non-conductive when it is OFF.
* The alarm for the flow rate and that for the temperature can be set independently.
If you have any query regarding our products or services, please feel free to contact us.
TEL: +81-42 756 7567
FAX: +81-42 752 2004
Email: info@rgl.co.jp
|